3.3.3 Offset adjustment with integral factor

The integral factor MP1080 also results in an automatic offset adjustment. It is only effective in the
stop condition (see block diagram of control loop).

According to the size of the factor the offset voltage will be reduced quickly or slowly.

Even a small amount of play in the drives can lead to instability in the control loop. An integral factor
of 0 is entered in this case.

Voltage
step
(0.6 mV)

t [s]

2

4

6

8

10

1

2

3

MP1080 ·s

a

= 1000

MP1080 ·s

a

= 500

MP1080 ·s

a

= 150

MP1080

Integral factor
Input value: 0 to 65535

MP1080.0

Integral factor X axis

MP1080.1

Integral factor Y axis

MP1080.2

Integral factor Z axis

MP1080.3

Integral factor 4th axis