8/95

TNC 360

5 EMERGENCY STOP Routine

4-107

5.1 Connection diagram

Under fault conditions the "control is ready" output should switch off the 24-volt supply. Because of
the enormous importance of this function this output is tested by the control every time the mains
power is switched on.

HEIDENHAIN recommends the following wiring:

This diagram represents a proposal for circuitry. The machine tool builder is responsible for
complying with applicable safety regulations.

+ -

Logic unit

After control voltage is switched on, the switch is opened

by each microprocessor for a short time.

X21/34 X24/2 X24/1 X22/4

"Control

is ready"

24V cannot
be switched
off

24V can be
switched off

Acknowledgement
"Control is ready"

EMERGENCY STOP
buttons

Control
voltage
on

k1

k1

K1

24 V

PLC