8/95

TNC 360

1 PLC Positioning Module

10-5

1.3 EMERGENCY STOP routine

After the TNC has been switched on, the internal EMERGENCY STOP switch-off is checked, i.e. for
each processor the power supply is briefly switched off.

Appropriate circuitry must ensure that the positioning module does not function if an error occurs
during the NC check, i.e. that the voltage for the acknowledgment is mutually switched off. The
circuit illustrated below can fulfill this function. The check is started at the same time that the control
voltage is switched on.

+ –

LE 407/415

After control voltage is switched on, the switch is opened

by each microprocessor for a short time.

X41/34 X44/2 X44/1 X42/4

"Control

operational"

24V Cannot
be switched
off

24V Can be
switched off

Acknowledgement
"Control operational"

EMERGENCY STOP
buttons

Control
voltage
on

k1

k1

K1

24 V

PLC

+ –

LE 234.003

After control voltage is switched on, the switch is opened

by each microprocessor for a short time.

X21/34 X24/2 X24/1 X22/4

EMERGENC STOP
buttons

Control
voltage
on

k1

k3

K3

24 V

PLC

k3

"Control

operational"

24V Cannot
be switched
off

24V Can be
switched off

Acknowledgement
"Control operational"