3-24

TNC 360

6 Nominal Value Output

8/95

The housing of the connection box must be electrically connected with the frame of the machine.
The 0 V of the nominal value differential input must be joined to signal ground, (cable cross-section

Ø 6 mm², see also under "Grounding diagram").

Suggested solution for connecting and wiring the screening in the connection box:

Insulated against housing

Leads are provided
with en sleeves.

Cable screens are led onto 0.14 mm

2

insulated strands via crimp eyelets.

SERVO

1 2 3 4 5 6 7 8 9 1 0 11 12 13 14 15 16

LE

X

Y

Z

S

IV

Pin Number

Assignment

1

Noml. value output

X axis

2

Noml. value output 0 V

X axis

3

Noml. value output

Y axis

4

Noml. value output 0 V

Y axis

5

Noml. value output

Z axis

6

Noml. value output 0 V

Z axis

7

Noml. value input IV axis

8

Noml. value input 0 V

IV axis

9

Analog input

10

Analog input 0 V

11

Noml. value output

S axis

12

Noml. value output 0 V

S axis

13

Screen connection

14

Screen connection

15

Screen connection

16

Screen connection

If the manufacturers want to use their own cable, HEIDENHAIN offers a 15-pin D-sub connector
with solderable leads (Id.-Nr. 243 971 ZY).

Leads are provided
with end sleeves.