4.3 LIO-06 Module Details

4.3.1 MIXIO Configuration

100

( 2 ) MIXO Configuration Details

The following items are displayed in the MIXIO Window. The discrete inputs/outputs, interrupt inputs, and analog
inputs/outputs can be set.

After changing the MIXIO configuration, save the definition data by selecting File – Save & Save into flash memory
from the main menu.

D : Enable or disable each item by clicking on the cell.

: Enabled,

: Disabled

REG : Displays the register number allocated to the inputs or outputs. It cannot be changed.

Word : Displays the word size of the register data. It cannot be changed.

The register length of discrete inputs/outputs is fixed at one word; 16 points are set for each input or
output register, and 8 points of the input or output register are allocated to the lower bytes. The reg-
ister length of the analog inputs/outputs is fixed at one word.

SCAN : Select the speed from HIGH, LOW, or NA (none specified), for the scan that processes the inputs

or outputs.

Current :

(Current Value)

The current value of the register will be displayed in binary when online. It will not be displayed
when offline.
The outputs to external devices can be set by changing the current value of the discrete outputs.
When the set value is confirmed, it is immediately saved in the register.
Other current values cannot be changed.

HEX : The current value of the register will be displayed in hexadecimal when online. It will not be dis-

played when offline.

Unit : Displays the unit [V] of the analog input/output current value

For the range of -10.000 to +10.000 analog input value, [V] is displayed in the Unit. However,
when the input value is out of this range, [V Above] is displayed and the Current (Current Value)
will be fixed to 10.000 or -10.000.

<Example>
Analog Input Value

Current Value

Unit

9.999 V

9.999

[V]

10.000 V

10.000

[V]

10.001 V

10.000

[V Above]

-9.999 V

-9.999

[V]

-10.000 V

-10.000

[V]

-10.001 V

-10.000

[V Above]

DATA : Displays the analog input/output register value with parentheses.

<Example>

Analog Input Register Value

DATA

IW†††† = 12345

[12345]

IW†††† = -12345

[-12345]