4.4 Details of Counter Functions

4.4.2 Pulse Count Function

112

4.4.2 Pulse Count Function

The Pulse Count Function reads A/B pulse input signals to increment (forward run) or decrement (reverse run) the
count.
The following graph shows changes in the pulse count for each run mode.

<Explanation>

Current counter value

The values of n1 to n7 (counter value at each scan) is displayed sequentially in Counter Value (IL……04).

Count preset (1)

Executing the Count preset at the position p1 forces the counter value to change to the preset value (p2
value).

MAX overflow

When the counter value increases to the value MAX (p3), the counter value will be automatically reset to the
value MIN (p4).

MIN overflow

When the counter value decreases to the value MIN (p5), the counter value will be automatically reset to the
value MAX (p6).

Count preset (2)

Executing the Count preset at the position p7 forces the counter value to change to the preset value (p8
value).

n1

n2

n3

n4

n5

n6

p2

p8

n7

n1

n2

n3

n4

n5

n6

n7

Ts

Count preset data

0

㧔㧗㧕

㧔㧙㧕

2147483647

㧔MAX㧕

2147483648㧔MIN㧕

p2

p1

p7

p8

p3

p6

p4

p5

Counter
count
register
value

Current counter
value display

Time (s)

Cancel count prohibit

Count prohibit

Count preset (1)

Ts

㧩 Scan time (s)

Count preset (2)

Cancel count prohibit

Count prohibit