4.2 Specifications of LIO-06 Module Connections

4.2.4 Digital Output Circuit

94

4.2.4 Digital Output Circuit

The following table shows the LIO-06 Module digital output circuit specifications.

Fig. 4.4 Digital Output Circuit (Sink Mode Output)

Item

Specifications

Outputs

8 points

Output Format

Transistor, open collector sink mode output

Isolation Method

Photocoupler

Output Voltage

+24 VDC,

±

20%

Output Current

100 mA max.

Leakage Current When
OFF

0.1 mA max.

ON Time/OFF Time

ON: 0.25 ms max.
OFF: 1 ms max.

Number of Commons

1 (8 points/common)

Protection Circuit

Fuse
The fuse is not, however, for circuit protection. It is for protecting against fire at output shorts.
Attach a fuse externally to each output if circuit protection is required.

Error Detection

Fuse blown detection
Replace the Module when fuse blown is detected.

Other Functions

DO_07 is shared with counter coincidence output.

0

24

DO_24V

Internal
circuit

DO_OUT

DO_COM

+24V

R

R