5.1 Outline of DO-01 Module

5.1.4 LED Indicators

124

( 2 ) Environmental Conditions

5.1.4 LED Indicators

The following table shows the DO-01 Module status when each indicator lamp is lit or unlit.

Item

Specifications

Environmental
Conditions

Ambient Operating
Temperature

0

to 55°C

Ambient Storage
Temperature

-25

to 85°C

Ambient Operating
Humidity

30% to 95% (with no condensation)

Ambient Storage
Humidity

5% to 95% (with no condensation)

Pollution Level

Pollution level 1 (conforming to JIS B 3501)

Corrosive Gas

There must be no combustible or corrosive gas.

Operating Altitude

2,000 m above sea level or lower

Mechanical
Operating
Conditions

Vibration Resistance

Conforming to JIS B 3502:

• 10 to 57 Hz with single-amplitude of 0.075 mm
• 57 to 150 Hz with fixed acceleration of 9.8 m/s

2

• 10 sweeps each in X, Y, and Z directions

(sweep time: 1 octave/min)

Shock Resistance

Conforming to JIS B 3502:
Peak acceleration of 147 m/s

2

twice for 11 ms each in the X, Y, and Z direc-

tions

Electrical
Operating
Conditions

Noise Resistance

Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Power supply noise (FT noise): 2 kV min., for one minute
Radiation noise (FT noise): 1 kV min., for one minute
Ground noise (impulse noise): 1 kV min., for 10 minutes
Electrostatic noise (contact discharge): 4 kV min., for 10 times

Installation
Requirements

Ground

Ground to 100

Ω max.

Cooling Method

Natural cooling

Indicator

Color

When Lit

When Unlit

RUN

Green

Normal operation

Error occurrence

FUSE

Red

One or some of the output protection
fuses is blown out.

Output protection fuses are normal.