4.2 Specifications of LIO-06 Module Connections

4.2.9 Wiring for Noise Control

98

Œ

Ground the cable shield between the external devices and the junction-terminal block on the external-device end.

4.2.9 Wiring for Noise Control

When the LIO-06 Module is mounted and used in an environment where there is high-frequency noise from an external
device, the counter may not correctly execute counting. In this case, install a noise filter or a ferrite core to suppress the
high-frequency noise.
The following figure shows an example of installing a noise filter and ferrite cores.

„

Recommended Parts

Œ

A fuse is inserted in the output common line of the LIO-06 Module for circuit protection. However, the fuse
may not be blown out in the cases such as layer shorts in outputs. To ensecure the circuit protection, pro-
vide a protective element such as fuse in each output as shown in the above diagram.

Œ

5 V, 12 V, and 24 V are available for phase-Z input voltage.
Note that the pin that is used will differ, depending on the input voltage.
Using the wrong pin may cause an accident.
At 5 V input: Use No.9 pin.
At 12 V input: Use No.34 pin.
At 24 V input: Use No.10 pin.

Œ

If you connect an inductive load, connect a diode parallel to the load to
absorb counter electromotive force.

Œ

Backward voltage: 10 times the load voltage or greater

Œ

Forward current: Load current or greater

OUT

diode

Source circuit


+

COM

Inductive

load

LIO-06

MP2000

Series

Machine

Controller

Noise

filter

Power

supply

Terminal

block

External device

Ferrite core

Ferrite core

Name

Model

Manufacturer

Ferrite core

E04SR301334

Seiwa Electric MFG. Co. Ltd.

Noise filter

LF-210N

NEC TOKIN Corporation

Advertising