4.2 Specifications of LIO-06 Module Connections

4.2.5 Analog Input Circuit

95

4

LIO-06 Module

4.2.5 Analog Input Circuit

The following table shows the LIO-06 Module analog input circuit specifications.

* Input conversion time = Delay time from input filter (1 ms max.) + 50

μs;

Delay time from the input filter peaks at 1 ms between -10 and +10 V.

4.2.6 Analog Output Circuit

The following table shows the LIO-06 Module analog output circuit specifications.

Item

Specifications

Number of Channels

1 channel

Isolation Method

Non-isolated

Analog Input Range

-10 to +10 V

Max. Rated Input

±15 V

Input Impedance

Approx. 20 k

Ω

Resolution

16 bits (-31276 to +31276)

Accuracy

25

°C

±0.1% (±10 mV)

0 to 50

°C

±0.3% (±30 mV)

Input Conversion Time *

1.05 ms max.

Item

Specifications

Number of Channels

1 channel

Isolation Method

Non-isolated

Analog Output Range

-10 to +10 V

Output Impedance

20 k

Ω max.

Resolution

16 bits (-31276 to +31276)

Accuracy

25

°C

±0.1% (±10 mV)

0 to 50

°C

±0.3% (±30 mV)

Max. Allowable Load Current

±5 mA

Output Delay Time

1.2 ms (after change with a full scale of -10 to +10 V)