8 lio-06 module connections, Lio-06 module – Yaskawa MP2000 Series I/O Module User Manual User Manual
Page 97

4.2 Specifications of LIO-06 Module Connections
4.2.8 LIO-06 Module Connections
97
4
LIO-06 Module
4.2.8 LIO-06 Module Connections
The following diagram shows connection example for LIO-06 Module connectors.
LIO-06
+15V
-15V
1
AO
AO_GND
26
+15V
-15V
2
AI
AI_GND
27
L
-10 to +10 V
FG
-10 to +10 V
FG
Junction-terminal block
External Device
External Device
Pulse Generator
V
4
5
PA+
PA-
0V
+5V
FG
㪂
㪄
29
30
PB+
PB-
6
GND
31
GND
9
PILC
㧔5V㧕
35
PIL
10
PILC
㧔24V㧕
34
PILC
㧔12V㧕
13
DICOM
38
DICOM
14
DI_00
39
DI_01
Latch input
External input signals
External input signals
15
DI_02
40
DI_03
16
DI_04
41
DI_05
17
DI_06
42
DI_07
+5V
20
DO_24V
45
DO_24V
21
DO_00
46
DO_01
L
L
22
DO_02
47
DO_03
L
L
23
DO_04
48
DO_05
L
L
24
DO_06
49
DO_07
L
L
25
DO_GND
50
DO_GND
FG (connector shell)
Fuse blown
detection circuit
Digital output
Digital input
Pulse input
Analog input
Analog output
Phase Z
latch input