Environmental conditions – Yaskawa MP2000 Series I/O Module User Manual User Manual

Page 32

Advertising
background image

2.1 Outline of LIO-01/LIO-02 Modules

2.1.3 Specifications

32

( 2 )

Environmental Conditions

Item

Specifications

Environmental
Conditions

Ambient Operating
Temperature

0 to 55

°C

Ambient Storage
Temperature

-25 to 85

°C

Ambient Operating
Humidity

30% to 95% (with no condensation)

Ambient Storage
Humidity

5% to 95% (with no condensation)

Pollution Level

Pollution level 1 (conforming to JIS B 3501)

Corrosive Gas

There must be no combustible or corrosive gas.

Operating Altitude

2,000 m above sea level or lower

Mechanical Operating
Conditions

Vibration Resistance

Conforming to JIS B 3502:

• 10 to 57 Hz with single-amplitude of 0.075 mm
• 57 to 150 Hz with fixed acceleration of 9.8 m/s

2

• 10 sweeps each in X, Y, and Z directions

(sweep time: 1 octave/min)

Shock Resistance

Conforming to JIS B 3502:
Peak acceleration of 147 m/s

2

twice for 11 ms each in the X, Y, and Z direc-

tions

Electrical Operating
Conditions

Noise Resistance

Conforming to EN 61000-6-2, EN 55011 (Group 1, Class A)
Power supply noise (FT noise): 2 kVmin., for one minute
Radiation noise (FT noise): 1 kVmin., for one minute
Ground noise (impulse noise): 1 kVmin, for 10 minutes
Electrostatic noise (contact discharge): 4 kVmin, for 10 times

Installation
Requirements

Ground

Ground to 100

Ω max.

Cooling Method

Natural cooling

Advertising