7.1.3 Hardware

Specifications

Specification Value
Backplane Current Load

800 mA @ 5 V

Operating Temperature

0 to 60°C (32 to 140°F)

Storage Temperature

-40 to 85°C (-40 to 185°F)

Relative Humidity

5% to 95% (non-condensing)

Vibration

Sine vibration 4-100 Hz in each of the 3 orthogonal axes

Shock

30G, 11 mSec. in each of the 3 orthogonal axes

LED Indicators

Module Status
Backplane Transfer Status
Serial Port Activity LED
Serial Activity and Error LED Status

Configuration Serial Port (PRT1)

DB-9M PC Compatible
RS-232 only
No hardware handshaking

Application Serial Ports

(PRT2, PRT3)
DB-9M PC Compatible
RS-232/422/485 jumper selectable
RS-422/485 screw termination included
RS-232 handshaking configurable
500V Optical isolation from backplane

7.1.4 Functional

Specifications

Built in accordance to the approved international specification
Two independent master ports completely user configurable
Support for balanced and unbalanced mode
Up to 32 sessions
Up to five sectors (separate databases) for each session
Individual database definition for each sector
1000 commands to control stations
Processor can issue control commands directly to the module or a controlled

device (10 at each scan)

Pass-through of event messages from controlled device to processor for

logging of time-tagged events

Supports clock synchronization from/to the processor
Receives events from the slave and sends them to the processor
Supports monitored data

o

Single-point

o

Double-point

o

Step-point

o

Measured-point

o

Bitstring 32-bit

o

Integrated total point

Class 1 and Class 2 delay parameter in the configuration file
Complete set up and monitoring of module through Unity Pro XL or Concept

software and user constructed configuration file (IEC101M.CFG)

All data related to the module is contained in user data files to simplify

monitoring and interfacing with the module