Module Configuration

PTQ-101M ♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 83 of 181

May 14, 2008

Read Command
The format of this field for the Read (102) command is as follows:

Read Command

Bit

0

to

15

Description

Not Utilized

No database value is associated with the construction of this command and no
qualifier value is used in this release of the software.

Clock Synchronization
The format of this field for the Clock Synchronization (103) command is as
follows:

Clock Synchronization Command

Bit

0
1
0

to

15

Description

Not Utilized

Synchronization Mode

Qualifier

No database value is associated with the construction of this command.

The Qualifier Parameter for this command has one of the following values:

0=Clock synchronization with out delay utilized
1=Synchronize clock with delay set
2=Measure delay, load delay then synchronize clock

Test Command

The format of this field for the test command (104 and 107) is as follows:

Test Command (both 101 and 104 versions)

Bit

0

to

15

Description

Not Utilized

No database value is associated with the construction of this command and no
qualifier value is used in this release of the software.