PTQ-101M ♦ Quantum Platform

Module Configuration

IEC 60870-5-101 Master Communication Module

Page 74 of 181

ProSoft Technology, Inc.

May 14, 2008

Class 1 Pend Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between class
1 polls for pending data.

Class 2 Pend Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between class
2 polls for pending data.

Class 1 Poll Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between each
class 1 poll.

Class 2 Poll Delay

0 to 2^32-1

This parameter sets the minimum number of milliseconds to delay between each
class 2 poll.

Auto Clock Req Mode

0=Sync Only, 1=Load delay/sync, 2=Acquire delay/load delay/sync

This parameter specifies the method used to perform automatic clock
synchronization. 0 performs a synchronization without delay, 1 performs
synchronization using the fixed Propagation Delay and 2 computes the delay and
use this value when synchronization takes place.

Propagation Delay

0 to 65535

This parameter sets the fixed propagation delay to be utilized if the Auto Clock
Req Mode parameter is set to a value of 1.

Response Timeout

0 to 2^32-1

This parameter sets the maximum number of milliseconds to wait for a
confirmation from the controlled station to a request from this module.