Rs-422, Rs-485 and rs-422 tip, Ptq-101m status data area – ProSoft Technology PTQ-101M User Manual

Page 152: Error/status data format

Advertising
background image

PTQ-101M ♦ Quantum Platform

Reference

IEC 60870-5-101 Master Communication Module

Page 152 of 181

ProSoft Technology, Inc.

May 14, 2008

7.4.4 RS-422

RS-485 and RS-422 Tip

If communication in the RS-422/RS-485 mode does not work at first, despite all
attempts, try switching termination polarities. Some manufacturers interpret +/-
and A/B polarities differently.

7.5

PTQ-101M Status Data Area

This section contains a listing of the data contained in the PTQ-101M status data
object, configuration error word and module error codes.

7.5.1 Error/Status Data Format

Offset Parameter Description

0 Scan

Count

This status value contains a counter incremented on each scan of the
module's main loop.

1 to 2

Product Name

This two-word data area contains the text values representing the
product name. These words contain the text '87S5' for the PTQ
platform.

3 to 4

Revision

This two-word data area contains the text values for the revision
number.

5 to 6

Op Sys #

This two-word data area contains the text values for the operating
system number.

7 to 8

Run Number

This two-word data area contains the text values for the run number.

9

Read Blk Cnt

This word contains the total number of block read operations
successfully executed.

10

Write Blk Cnt

This word contains the total number of block write operations
successfully executed.

11

Parse Blk Cnt

This word contains the total number of write blocks successfully
parsed.

12

Error Blk Cnt

This word contains the total number of block transfer errors.

13

Event Msg Cnt This word contains the number of event messages waiting to send to

the processor.

Advertising