ProSoft Technology PTQ-101M User Manual

Page 166

Advertising
background image

PTQ-101M ♦ Quantum Platform

Reference

IEC 60870-5-101 Master Communication Module

Page 166 of 181

ProSoft Technology, Inc.

May 14, 2008

<34> := Measured value, normalized value with time tag CP56Time2A

M_ME_TD_1

<35> := Measured value, scaled value with time tag CP56Time2A

M_ME_TE_1

<36> := Measured value, short floating point value with time tag

CP56Time2A M_ME_TF_1

<37> := Integrated totals with time tag CP56Time2A M_IT_TB_1

<38> := Event of protection equipment with time tag CP56Time2A

M_EP_TD_1

<39> := Packed start events of protection equipment with time tag

CP56time2A M_EP_TE_1

<40> := Packed output circuit information of protection equipment with

time tag CPT56Time2a M_EP_TF_1

Process information in control direction

(station-specific parameter)

<45> := Single command C_SC_NA_1

<46> := Double command C_DC_NA_1

<47> := Regulating step command C_RC_NA_1

<48> := Set point command, normalized value C_SE_NA_1

<49> := Set point command, scaled value C_SE_NB_1

<50> := Set point command, short floating point value C_SE_NC_1

<51> := Bitstring of 32 bit C_BO_NA_1

System information in monitor direction

(station-specific parameter)

<70> := End of initialization M_EI_NA_1

System information in control direction

(station-specific parameter)

<100> := Interrogation command C_IC_NA_1

<101> := Counter interrogation command C_CI_NA_1

<102> := Read command C_RD_NA_1

<103> := Clock synchronization command C_CS_NA_1

<104> := Test command C_TS_NB_1

<105> := Reset process command C_RP_NC_1

<106> := Delay acquisition command C_CD_NA_1

Parameter in control direction

(station-specific parameter)