PTQ-101M ♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 85 of 181

May 14, 2008

The Qualifier Parameter used with this command is determined by summing the
options from lists that follow:

Kind of parameter:

0=Not

used

1=Threshold

value

2=Smoothing factor (filter time constant)
3=Low limit for transmission of measured values
3=High limit for transmission of measured values
5 to 31 = Reserved by standard
32 to 63 = Reserved for special use (private range)

Local parameter change:

0=No

change

64=Change

Parameter in operation:

0=Operation
128=Not in operation

Parameter Activation

The format of this field for the Parameter Activation (113) is as follows:

Parameter Activation Command

Bit

0

to

7
8
9

to

15

Not Utilized

Activation Qualifier

Description

Parameter Qualifier

No database value used with the construction of this command.

The Qualifier Parameter used with the command is determined by summing the
options from the lists that follow:

Parameter Qualifier:

0=Not

used

1=Act/Deact of previously loaded parameters (point index = 0)
2=Act/Deact of the parameter of the point index specified
3=Act/Deact of persistent cyclic or periodic transmission of the addressed

object

4 to 127 = Reserved by standard
128 to 255 = Reserved for special use (private range)