Module Configuration

PTQ-101M ♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 69 of 181

May 14, 2008

The following example shows a sample [Backplane Configuration] section:

[Backplane Configuration]

Module Name: PTQ-101M SAMPLE TEST MODULE

#These values are required to define the data area to transfer between the

#module and the processor.

Read Register Start : 0 #Database start register to move to processor

Read Register Count : 50 #Number of words moved from module to

#processor

Write Register Start: 1000 #Database start register where data placed

#from processor

Write Register Count: 50 #Number of words moved from processor to

#module

#Used to define the area in the Processor for the module to interface with

3x Register Start: 1 #3x start register where data moved from

#module to processor (1-n)

4x Register Start: 1 #4x start register where data moved from

#processor to module (1-n)

Pass-Through Events : N #Pass event messages to processor

Modify each of the parameters based on the needs of your application.

Module Name

0 to 80 characters

This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the
configuration file.

Read Register Start

Range 0 to 3999

This parameter specifies the starting register in the module where the data
transferred from the processor will be placed. Valid range for this parameter is 0
to 3999.

Read Register Count

Range 0 to 3999

This parameter specifies the number of registers to be transferred from the
module to the processor. Valid entry for this parameter is 0 to 3999.

Write Register Start

0 to 3999

The Write Register Start parameter assigns the starting address for data to
retrieve from the processor.

Advertising