Command list error data block (9950) – ProSoft Technology PTQ-101M User Manual

Page 137

Advertising
background image

Reference PTQ-101M

♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 137 of 181

May 14, 2008

Word Offset

Definitions

Description

2 COT

This field contains the COT for the event message
received from the IED. If the size of the COT is a
single byte, the originator address will always be zero.
The COT is in the LSB and the originator address is in
the MSB.

3 Reserved

This field is reserved for future use and is added here
to keep the structure double-word aligned for all
platforms.

4 to 5

Point Index

This field contains the point index in the remote device
that generated the event.

6 ASDU

Type

This field contains the ASDU type code for the data
contained in the message.

7

Milliseconds
and Seconds

This word contains the seconds and milliseconds
when the event occurred.

8

Minutes and
Hours

This field contains the minutes and hours the event
occurred.

9

Month and Day This field contains the month and day of the month the

event occurred.

10

Year

This field contains the year the event occurred.

11 Qualifier

This field contains the point qualifier, quality or
sequence value as described in the protocol
specification.

12 to 13

Value

This field contains the a double word value for the
point associated with the event message.

Command List Error Data Block (9950)
Block 9950 identification code is used to request the Command List Error Table
from the module. The format for the block is shown below:

Block Format from Processor (4x Register Data)

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the user
wishes to request a new command block.

1 Block

ID

This field contains the value of 9950 identifying the
block type to the module.

2

Number of
Commands to
report

This field contains the number of commands to report
in the response message. The value has a range of 1
to 60.

3

Start Index of
First
Command

This parameter sets the index in the command list
where to start. The first command in the list has a
value of 0. The last index in the list has a value of
MaxCommands - 1.

4 to 63

Spare

Not Used

Response to a block 9950 request: The module will respond to a valid request
with a block containing the requested error information. The format for the block
is shown below: