Cable connections, Ptq-101m, Status data area – ProSoft Technology PTQ-101M User Manual

Page 148

Advertising
background image

PTQ-101M ♦ Quantum Platform

Reference

IEC 60870-5-101 Master Communication Module

Page 148 of 181

ProSoft Technology, Inc.

May 14, 2008

For the PTQ-101M, the control and monitor points would be transferred as shown
in the following illustration.

Processor

101M

Module

Slave

Monitor

Points

Control

Points

Monitor

Points

Control

Points

You must make sure that all points are configured in the correct location in the
PTQ-101M module database in order to be properly updated from/to the
processor.

7.4 Cable

Connections

The application ports on the PTQ-101M module support RS-232, RS-422, and
RS-485 interfaces. Please inspect the module to ensure that the jumpers are set
correctly to correspond with the type of interface you are using.

Note: When using RS-232 with radio modem applications, some radios or modems require
hardware handshaking (control and monitoring of modem signal lines). Enable this in the
configuration of the module by setting the UseCTS parameter to 1.