Event message block (9903) – ProSoft Technology PTQ-101M User Manual

Page 136

Advertising
background image

PTQ-101M ♦ Quantum Platform

Reference

IEC 60870-5-101 Master Communication Module

Page 136 of 181

ProSoft Technology, Inc.

May 14, 2008

Block Format from Module (3x Register Data)

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the block is
handled.

1 Block

ID

This field contains the block identification code of
9902 for the block.

Event Message Block (9903)

Block identification code 9903 is used to request event messages received on
the master port for the processor.

Block Format from Processor (4x Register Data)

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the user
wishes to request a new command block.

1 Block

ID

This field contains the value of 9903 to request event
data

2 to 63

Spare

Not used

Block Format from Module (3x Register Data)

Word Offset in Block

Data Field(s)

Description

0

Sequence
Counter

This field contains a new value each time the block is
handled.

1 Block

ID

This field contains the block identification code of
9903 for the block.

2 Event

Count

This field contains the number of events present in the
block. Values of 1 to 4 are valid.

3-16

Event 1

Event message

17-30

Event 2

Event message

31-44

Event 3

Event message

45-58

Event 4

Event message

59-61 Spare

Not

used

62

Event count in
queue

Number of events in queue still waiting to send

63

Event Overflow Event buffer overflow

The format of each 14 word data region in the block is as follows:

Word Offset

Definitions

Description

0 Session

Index

This field contains the session index used to define
the controlled unit in the module from which the event
was generated.

1 Sector

Index

This field contains the sector index used to define the
database within the controlled unit from which the
event was generated.

Advertising