Reference PTQ-101M

♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 159 of 181

May 14, 2008

[Section]/Item Value

Range

Description

C1/C2 Poll Count Pend:

0 to 65535 This parameter sets the maximum number of

class 1 and class 2 polls performed on this
session before trying the next session. This
parameter prevents a session from monopolizing
the communication port.

Class 1 Polls:

0 to 65535 This parameter sets the maximum number of

class one polls performed on this session before
switching to another session. This parameter
prevents a session from monopolizing the
communication port.

Class 1 Pend Delay:

0 to 2^32-1 This parameter sets the minimum number of

milliseconds to delay between class 1 polls for
pending data.

Class 2 Pend Delay:

0 to 2^32-1 This parameter sets the minimum number of

milliseconds to delay between class 2 polls for
pending data.

Class 1 Poll Delay:

0 to 2^32-1 This parameter sets the minimum number of

milliseconds to delay between each class 1 poll.

Class 2 Poll Delay:

0 to 2^32-1 This parameter sets the minimum number of

milliseconds to delay between each class 2 poll.

Auto Clock Req Mode:

0, 1 or 2

This parameter specifies the method used to
perform automatic clock synchronization. 0
performs a synchronization without delay, 1
performs synchronization using the fixed
Propagation Delay and 2 computes the delay and
use this value when synchronization takes place.

Propagation Delay:

0 to 65535 This parameter sets the fixed propagation delay to

be utilized if the Auto Clock Req Mode parameter
is set to a value of 1.

Response Timeout:

0 to 2^32-1 This parameter sets the maximum number of

milliseconds to wait for a confirmation from the
controlled station to a request from this module.

ACTTERM with setpoint:

Yes or No

This parameter specifies what the last message
will be in the response to a setpoint command. If
the parameter is set to Yes, an ACTTERM will be
the last response, and if set to No, ACTCON will
be the last response.

[Section]/Item Value

Range

Description

[IEC-101 MASTER
SESSION x SECTOR y]

This section sets the parameters for a specific
sector of a session.

Common ASDU Address:

0 to 255 (1
oct) or 0 to
65535 (2 oct)

This parameter sets the common ASDU address
to association with this sector of the specified
session. The range of address for this parameter
are dependent on the length value set in the
session section.