Point index, Qualifier parameter, Single point, double point, and regulating setup – ProSoft Technology PTQ-101M User Manual

Page 78

Advertising
background image

PTQ-101M ♦ Quantum Platform

Module Configuration

IEC 60870-5-101 Master Communication Module

Page 78 of 181

ProSoft Technology, Inc.

May 14, 2008

Type

Description

DB Index type

100

Group interrogation command

NA

101

Counter interrogation command

NA

102 Read

command

NA

103 Clock

Synchronization

NA

104

Test command (101 standard)

NA

105

Reset process command

NA

107

Test command (104 standard)

NA

110

Parameter, normalized measured value

Word address

111

Parameter, scaled measured value

Word address

112

Parameter, short float value

Double-word address

113

Parameter activation command

NA

242

BCD integrated setpoint command

3 word address

255

Send a class 2 poll

NA

Point Index

Point Index field specifies the address in the remote slave device of the point to
interact with.

Qualifier Parameter

The Qualifier Parameter field defined for a command is dependent on the data
type used in the command. In order to compute the qualifier for a command, add
all the values for the features to use with a command together to form a single
number. This number should be entered in the command record. Each data set is
discussed below:

Single Point, Double Point, and Regulating Setup

The format of the field for Single Point (45), Double Point (46), and Regulating
Step (47)

commands is as follows:

Single Point, Double Point and Regulating Step Point Commands

Bit

Single

Double

Step

0

Value

Control

Control

1

0

Value

Value

2
3
4
5
6
7
8
9

10

to

15

Select/Execute Code

Qualifier Code

Not Utilized

Deselect Code

Use Override Value