Diagnostics and Troubleshooting

PTQ-101M ♦ Quantum Platform

IEC 60870-5-101 Master Communication Module

ProSoft Technology, Inc.

Page 95 of 181

May 14, 2008

6.3 Required

Software

In order to send and receive data over the serial port (COM port) on your
computer to the module, you must use a communication program (terminal
emulator).

A simple communication program called HyperTerminal is pre-installed with
recent versions of Microsoft Windows operating systems. If you are connecting
from a machine running DOS, you must obtain and install a compatible
communication program. The following table lists communication programs that
have been tested by ProSoft Technology.

DOS

ProComm, as well as several other terminal emulation programs

Windows 3.1

Terminal

Windows 95/98

HyperTerminal

Windows NT/2000/XP

HyperTerminal

The module uses the Zmodem file transfer protocol to send (upload) and receive
(download) configuration files from your module. If you use a communication
program that is not on the list above, please be sure that it supports Zmodem file
transfers.

6.4

Using the Configuration/Debug Port

To connect to the module's Configuration/Debug port:

1

Connect your computer to the module's port using a null modem cable.

2

Start the communication program on your computer and configure the
communication parameters with the following settings:

Baud Rate

57,600

Parity None
Data Bits

8

Stop Bits

1

Software Handshaking

None

3

Open the connection. When you are connected, press the [?] key on your
keyboard. If the system is set up properly, you will see a menu with the
module name followed by a list of letters and the commands associated with
them.

If there is no response from the module, follow these steps:

1

Verify that the null modem cable is connected properly between your
computer's serial port and the module. A regular serial cable will not work.

2

Verify that another program is not controlling the COM port.

3

Verify that your communication software is using the correct settings for baud
rate, parity and handshaking.

4

On computers with more than one serial port, verify that your communication
program is connected to the same port that is connected to the module.

If you are still not able to establish a connection, you can contact ProSoft
Technology Technical Support for further assistance.