Block Format for Read
Block Format from Module (3x Register Data)

Word Offset in Block

Data Field(s)

Description

0 Sequence

Counter

This field contains a new value each time the
block is handled.

1 Block

ID

This field contains the block identification code
of 9903 for the block.

2 Event

Count

This field contains the number of events present
in the block. Values of 1 to 4 are valid.

3 to 16

Event 1

Event message

17 to 30

Event 2

Event message

31 to 44

Event 3

Event message

45 to 58

Event 4

Event message

59 to 61

Spare

Not used

62

Event count in queue

Number of events in queue still waiting to send

63

Event Overflow

Event buffer overflow

The format of each 14 word data region in the block is shown in the following
table.

Word Offset

Definitions

Description

0 Session

Index

This field contains the session index used to
define the controlled unit in the module from
which the event was generated.

1 Sector

Index

This field contains the sector index used to
define the database within the controlled unit
from which the event was generated.

2 COT

This field contains the COT for the event
message received from the IED. If the size of
the COT is a single byte, the originator address
will always be zero. The COT is in the LSB and
the originator address is in the MSB.

3 Reserved

This field is reserved for future use and is added
here to keep the structure double-word aligned
for all platforms.

4 to 5

Point Index

This field contains the point index in the remote
device that generated the event.

6 ASDU

Type

This field contains the ASDU type code for the
data contained in the message.

7

Milliseconds and
Seconds

This word contains the seconds and
milliseconds when the event occurred.

8

Minutes and Hours

This field contains the minutes and hours the
event occurred.

9

Month and Day

This field contains the month and day of the
month the event occurred.

10

Year

This field contains the year the event occurred.

11 Qualifier

This field contains the point qualifier, quality or
sequence value as described in the protocol
specification.

12 to 13

Value

This field contains the double word value for the
point associated with the event message.