Eoi time sync, Eoi general int, Database definition – ProSoft Technology PTQ-101M User Manual

Page 76: Iec-101 master commands

Advertising
background image

PTQ-101M ♦ Quantum Platform

Module Configuration

IEC 60870-5-101 Master Communication Module

Page 76 of 181

ProSoft Technology, Inc.

May 14, 2008

EOI Time Sync.

Yes or No

This parameter specifies if the sector in the controlled device will be sent a time
synchronization command after this module received an EOI message from the
controlled unit.

EOI General Int

Yes or No

This parameter specifies if the sector in the controlled device will be sent a
general interrogation command after this module received an EOI message from
the controlled unit.

Database Definition

Database definition for this session/sector.

Data Types are as follows:

Monitored Data

1 = Single point
3 = Double point
5 = Step point
7 = Bitstring of 32-bits
9 = Measured normalized points
11 = Measured scaled points
13 = Measured short float points
15 = Integrated totals
110 = Measured normalized parameter (word-addressing/1 point = 1 data

word)

111 = Measured scaled parameter (word-addressing/1 point = 1 data word)
112 = Measured short float parameters (double-word-addressing/1 point = 2

data words)

240 = Integrated totals BCD format (3 word-addressing/1 point = 3 data

words)

5.2.6 [IEC-101

Master

Commands]

This section contains the commands for the module. This section can contain up
to 1000 user defined commands to be executed by the module and sent to the
controlled devices. There is no need to place Class 1 or Class 2 polls in the this
list for the controlled devices as the master driver for each port will execute these
automatically when the port is idle. In order for the port to be idle, make sure that
there is idle time available and that the commands do not constantly utilize the
ports. The command list section starts with a reserved label START and ends
with the label END. Each row in the file corresponds to an individual command
with the first character position in each row left blank (white space).