Reset process, Parameter setting – ProSoft Technology PTQ-101M User Manual
Page 84

PTQ-101M ♦ Quantum Platform
Module Configuration
IEC 60870-5-101 Master Communication Module
Page 84 of 181
ProSoft Technology, Inc.
May 14, 2008
Reset Process
The format of this field for the Reset Process (105) command is as follows:
Reset Process Command
Bit
0
to
7
8
to
15
Description
Reset Qualifier
Not Utilized
No database value is associated with the construction of this command.
The Qualifier Parameter has one of the following values as define in the protocol
specification:
0=Not
used
1=General reset of process
2=Reset pending information with time tag of the event buffer
3 to 127 = Reserved by standard
128 to 255 = Reserved for special use (private range)
Parameter Setting
The format of this field for the Parameter Setting (110=Normalized,
111=Scaled, 112=Short float)
is as follows:
Parameter Setting (Normalized, Scaled, Short Float) Command
Bit
0
to
5
6
7
8
to
15
Description
Kind of Parameter
Not Utilized
Local change
Operation
The value from module's database utilized to build the command.