PTQ-101M ♦ Quantum Platform

Module Configuration

IEC 60870-5-101 Master Communication Module

Page 84 of 181

ProSoft Technology, Inc.

May 14, 2008

Reset Process
The format of this field for the Reset Process (105) command is as follows:

Reset Process Command

Bit

0

to

7
8

to

15

Description

Reset Qualifier

Not Utilized

No database value is associated with the construction of this command.

The Qualifier Parameter has one of the following values as define in the protocol
specification:

0=Not

used

1=General reset of process
2=Reset pending information with time tag of the event buffer
3 to 127 = Reserved by standard
128 to 255 = Reserved for special use (private range)

Parameter Setting

The format of this field for the Parameter Setting (110=Normalized,
111=Scaled, 112=Short float)

is as follows:

Parameter Setting (Normalized, Scaled, Short Float) Command

Bit

0

to

5
6
7
8

to

15

Description

Kind of Parameter

Not Utilized

Local change

Operation

The value from module's database utilized to build the command.