Configuration data definition, Configuration, Data definition – ProSoft Technology PTQ-101M User Manual

Page 156: 6 configuration data definition

Advertising
background image

PTQ-101M ♦ Quantum Platform

Reference

IEC 60870-5-101 Master Communication Module

Page 156 of 181

ProSoft Technology, Inc.

May 14, 2008

Error Description

602

Session not reserved

603 Illegal

session

604

Session is reserved

605

Session is not available

701

No memory to transmit message

702

ASDU not supported

703 Duplicate

request

704 Illegal

sector

705

Control mode is illegal

801

Partial stop request

802

Stop request failed

901 Response

timeout

902

Negative COT in response

903

Session is offline

904

Session is disabled

905

Select confirmation received, waiting to execute

906

Execute confirmation has not be received

7.6

Configuration Data Definition

This section contains a listing of the parameters and their definitions for the PTQ-
101M module configuration file definition (IEC101M.CFG).

[Section]/Item Value

Range

Description

[Backplane Configuration]

Backplane transfer parameters

Module Name:

0 to 80
characters

This parameter assigns a name to the module that
can be viewed using the configuration/debug port.
Use this parameter to identify the module and the
configuration file.

4x Register Start:

1 to n

This parameter sets the first register in the
processor where the data transferred from the
processor to the module is present.

Write Register Start:

0 to 3999

This parameter specifies the starting register in
the module where the data transferred from the
processor will be placed. Valid range for this
parameter is 0 to 3999.

Write Register Count:

0 to 4000

This parameter specifies the number of registers
to transfer from the processor to the module. Valid
entry for this parameter is 0 to 4000.

3x Register Start:

1 to n

This parameter sets the first register in the
processor where the data transferred from the
module to the processor will be placed.

Read Register Start:

0 to 3999

This parameter specifies the starting register in
the module where data will be transferred from the
module to the processor. Valid range for this
parameter is 0 to 3999.