9300 Servo PLC EN 5.0

Fault message

Remedy

Cause

Description

No.

Remedy

Cause

Description

Display

x061

CE0

Automation interface (AIF) communication
error

Faulty transfer of control commands via AIF.

·

Plug in the communication
module/keypad XT firmly, screw down, if
necessary.

·

Switch off monitoring (C0126 = 3).

x062

CE1

Communication error on the process data
input object CAN1_IN

CAN1_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/1, if necessary.

·

Switch off monitoring (C0591 = 3).

x063

CE2

Communication error on the process data
input object CAN2_IN

CAN2_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/2, if necessary.

·

Switch off monitoring (C0592 = 3).

x064

CE3

Communication error on the process data
input object CAN3_IN

CAN3_IN object receives faulty data or
communication is interrupted.

·

Check wiring at X4.

·

Check sender.

·

Increase monitoring time under
C0357/3, if necessary.

·

Switch off monitoring (C0593 = 3).

x065

CE4

BUS−OFF state of system bus (CAN)

The controller has received too many faulty
telegrams via the system bus (CAN) and has
disconnected from the bus.

·

Check wiring at X4: Is the bus correctly
terminated?

·

Check shield connection of the cables.

·

Check PE connection.

·

Check bus load, reduce the baud rate if
necessary. (Observe the cable length!)

·

Switch off the monitoring (C0595 = 3).

x066

CE5

Time−out of system bus (CAN)
(communication error of gateway function)

For remote parameterisation (C0370,
C0371) via system bus (CAN):

·

Slave does not respond.

·

Communication monitoring time has
been exceeded.

·

Check wiring of system bus (CAN).

·

Check CAN bus configuration.

0070

U15

Undervoltage of internal 15 V voltage supply

Check voltage supply.

x071

CCR

System fault

Strong interference on the control cables

Control cables must be shielded.

Ground or earth loops in wiring

·

Check wiring.

·

Check PE connection.

After fault correction: completely
deenergise the device (switch off 24 V
supply, discharge DC bus)!

0072

PR1

Checksum error in parameter set 1
CAUTION: The Lenze setting is loaded
automatically!

·

Fault when loading a parameter set.

·

Interruption while transmitting the
parameter set via keypad.

·

Set the required parameters and store
them under C0003 = 1.

·

As to PLC devices, check the use of
pointers.

The stored parameters are incompatible
with the loaded software version.

Store the parameter set under C0003 = 1
first to allow for a faults reset.

0074

PEr

Program error

Error in the program flow

Send the parameter set (on floppy
disk/CD−ROM) with a detailed description of
the problem to Lenze.
After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

0075

PR0

Error in parameter set.

The operating system software has been
updated.

Storage of the Lenze setting C0003 = 1.

After troubleshooting: Deenergise the
device completely (disconnect 24 V
supply, discharge DC bus)!

0079

PI

Fault during parameter initialisation

·

An error has been detected during
parameter set transfer between two
controllers.

·

Parameter set does not match the
controller, e.g. when data were
transmitted from a controller with more
performance to a controller with less
performance.

·

Correct parameter set.

·

Check code initialisation values.

After fault correction: completely
deenergise the device (switch off 24 V
supply, discharge DC bus)!

0080

PR6

Too many user codes

Reduce the number of user codes.

x: 0 = TRIP, 1 = Message, 2 = Warning, 3 = FAIL−QSP