Manual adaptation of motor data, 16 manual adaptation of motor data, 9300 servo plc – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 74: System blocks

Advertising
background image

2.12

MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−60

L

9300 Servo PLC EN 5.0

2.12.16

Manual adaptation of motor data

If you use a motor not listed in the selection under C0086, select a motor with similar data under
C0086 and adapt the motor data manually.

Note!

If the physical limit of the drive is considerably exceeded when a motor is configured via C0086 (e.g.:
EVS9321−EI with motor C0086=41 or C0086=42), this may cause a "No program" or "float sys−T.
error".

For more detailed information about commissioning, please refer to the Mounting Instructions for the
9300 Servo PLC!

·

The following codes help you to manually adapt the motor data:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

[C0006] Op mode

à

Operating mode of the motor control

à

Dependent on C0086

·

If C0086 is changed, the value is
reset to the assigned Lenze setting

·

Change of C0006 sets C0086 = 0!

·

ESC (Extended Speed Control):
Speed control with increased
speed control steadiness for
operation with incremental
encoder only (not resolver!).

2

Servo async Y

Servo control for asynchronous
motors in star connection

3

Servo PM−SM Y

Servo control for synchronous motors
in star connection

22

Servo async

Servo control for asynchronous
motors in delta connection

31

ASM Y − ESC

Servo control for asynchronous
motors in star connection, ESC

32

PM−SM Y − ESC

Servo control for synchronous motors
in star connection, ESC

33

ASM − ESC

Servo control for asynchronous
motors in delta connection, ESC

C0022 Imax current

à

I

max

limit

à

Dependent on C0086

·

If C0086 is changed, the value is
reset to the assigned Lenze setting
(1.5 * Imotor)

0

{0.01 A}

1.50 I

r

C0077 Vp field CTRL

0.25

Gain of field controller (V

pF

)

0.00

{0.01}

15.99

C0078 Tn field CTRL

15.0

Reset time of field controller (T

nF

)

1.0

{0.5 ms}

8000.0

8000 ms = switched off

[C0081] Mot power

à

Rated motor power according to
nameplate

à

Dependent on C0086

·

If C0086 is changed, the value is
reset to the assigned Lenze setting

·

Change sets C0086 = 0

0.01

{0.01 kW}

500.00