2.12.17.4

OC6 − I

2

x t overload monitoring

The I

2

× t load of the motor is continuously calculated by the controller and displayed in C0066.

I

2

x t monitoring is dimensioned in such a way that it is triggered after 179 s in case of a motor with

a thermal motor time constant of 5 minutes, a motor current of 1.5 x I

r

and a trigger threshold of

100 %.

Two adjustable trigger thresholds serve to define different responses.

·

Adjustable response OC8 (TRIP, warning, off).
– The response is set in C0606.
– The trigger threshold is set in C0127.
– The OC8 response can be used for advance warning.

·

Fixed response OC6−TRIP.
– The trigger threshold is set in C0120.

Behaviour of the I

2

x t monitoring

Condition

I

2

x t monitoring is deactivated.

C0066 = 0 % and

When C0120 = 0 % and C0127 = 0 %, set controller inhibit.

I

2

x t monitoring is stopped.

The current value in C0066 is frozen.

When C0120 = 0 % and C0127 = 0 %, activate controller enable.

I

2

x t monitoring is deactivated.

The motor utilisation is displayed in C0066.

Set C0606 = 3 (off) and C0127 > 0 %.

An error message OC6 or OC8 can only be reset if the I

2

× t load has exceeded the set trigger

threshold by 5 %.

Calculate release time

t + * (C0128) @ ln

ȧ

ȡ
Ȣ

1 *

y ) 1

ǒ

IM

Ir

Ǔ

2

@ 100

ȧ

ȣ
Ȥ

I

M

Actual motor current

I

r

Rated motor current

y

C0120 or C0127

·

The thermal loading capacity of the motor is expressed by the thermal motor time constant
(C0128). The value can be obtained from the rated motor data or contact the manufacturer of
the motor.

Read release time in the diagram

Diagram for detecting the release times of a motor with a thermal motor time constant of 5 min:

I

= 3 × I

mot

r

0

50

100

120

0

100

200

300

400

500

600

700

800

900

1000

t [s]

I t [%]

2

I

= 2 × I

mot

r

I

= 1.5 × I

mot

r

I

= 1 × I

mot

r

9300std105

Fig. 2−28

I

2

× t monitoring: Release times with different motor currents and trigger thresholds

Imot

Motor current

I

r

Rated motor current

I

2

t

I

2

t load

t

Time

Advertising