9300 servo plc, System blocks, 8 oh − heatsink temperature monitoring (fixed) – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 87

Advertising
background image

9300 Servo PLC

System blocks

2.12

MCTRL_MotorControl (node number 131)

2−73

L

9300 Servo PLC EN 5.0

2.12.17.8

OH − heatsink temperature monitoring (fixed)

This monitoring function protects the drive controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x050 OH

Heatsink temperature (fixed)

MCTRL_bKuehlGreaterSet−
Value_b

·

· Lenze setting

ü Setting possible

MCTRL_bKuehlGreaterSetValue_b is derived from a comparator with hysteresis. The switch−off
threshold and the hysteresis are fixed:

·

The switch−off threshold is 85 °C

·

The hysteresis is 5 K, i.e. the value for switching on again is 80 ºC.

The following causes can bring about an actuation of the monitoring process:

Cause

Remedy

The ambient temperature is too high.

Mount a blower in the control cabinet.

The drive controller is overloaded in the arithmetic mean, i. e. overload
and recovery phase exceed 100%.

·

Mount a blower in the control cabinet.

·

Shorten overload phase.

·

Use a more powerful drive controller.