2.12

MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−74

L

9300 Servo PLC EN 5.0

2.12.17.9

OH3 − motor temperature monitoring (fixed)

This monitoring function protects the motor against overheating.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x053 OH3

Motor temperature (fixed)

MCTRL_bMotorTempGreater−
SetValue_b

·

ü

· Lenze setting

ü Setting possible

MCTRL_bMotorTempGreaterSetValue_b is derived from a comparator with hysteresis. The
switch−off threshold and the hysteresis are fixed:

·

The switch−off threshold is 150 °C

·

The hysteresis is 15 K, i.e. the value for switching on again is 135 ºC.

This monitoring only applies to the temperature sensor specified by Lenze as it is, for instance,
included in the Lenze standard servo motor.

·

The Sub−D connectors X7 or X8 are available as inputs.

Stop!

The temperature sensor may either be connected to X7 or to X8; the respective other input for the
temperature sensor must be free!

This monitoring is active in the Lenze setting and is thus triggered when you use a non−Lenze servo
motor!

·

The response is set under C0583:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0583 MONIT OH3

à

Monitoring configuration: Motor
temperature
(Motor temperature > fixed limit
temperature)

à

Dependent on C0086

0

TRIP

3

Off