3.6

Code table

9300 Servo PLC

Appendix

3−28

L

9300 Servo PLC EN 5.0

Code

Info

Possible settings

LCD

Code

Info

Selection

Lenze

LCD

[C0089] Mot frequency

à

Rated motor frequency

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

·

Change sets C0086 = 0.

10

{1 Hz}

1000

[C0090] Mot voltage

à

Rated motor voltage

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

·

Change sets C0086 = 0.

50

{1 V}

500

[C0091] Mot cos phi

à

Motor cos

j

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

·

Change sets C0086 = 0.

0.50

{0.01}

1.00

C0093 DRIVE ident

g

Controller identification

0

Def. power stage

1

No power stage

93xx

93xx

C0094 Password

0

Keypad password protection

·

Parameter password protection for the keypad.

·

When the password is activated, only user−menu codes
can be accessed.

·

For extended password protection, please see C0096.

0

{1}

9999

0 = No password protection

[C0095] Rotor pos adj

0

Rotor position adjustment of a synchronous motor

·

C0058 displays the zero phase of the rotor

·

C0095 = 1 starts position adjustment

0

Not active

1

Active

C0096 AIF/CAN prot.

AIF/CAN password protection

·

Extended password protection for bus systems when
password is activated (C0094).

·

All codes in the user menu can be accessed.

0

No password protection

1

Read protection

2

Write protection

3

Read/write protection

1

0

AIF password protection

2

0

CAN password protection

C0098 Zero pos offs

0

Setting the reference position of the feedback system

·

For position feedback (integrator output
MCTRL_dnPos_p

of the motor control)

·

Only possible when the controller is inhibited.

·

Caution: This code returns an invalid value when it is
read.

−2147483647

{1 inc}

2147483647

C0099 S/W version

g

Software version of operating system

C0105 QSP Tif

0.000

Deceleration time for quick stop (QSP)

·

Referred to speed change n

max

(C0011) ... 0

0.000

{0.001 s}

999.900