C0361 Load IN/OUT
g
System bus: Bus load
·
Trouble−free operation demands that the total bus load
(all connected devices) does not exceed 80 %.
0
{1 %}
100
1
All sent (without free CAN objects)
2
All received (without free CAN objects)
3
Sent on CAN1_OUT
4
Sent on CAN2_OUT
5
Sent on CAN3_OUT
6
Sent on parameter data channel1
7
Sent on parameter data channel2
8
Received from CAN1_IN
9
Received from CAN2_IN
10
Received from CAN3_IN
11
Received from parameter data channel1
12
Received from parameter data channel2
C0362 Sync cycle
g
System bus: Time interval between 2 sync telegrams
(in preparation)
1
{1 ms}
30
C0363 Sync corr
1
System bus: Sync correction increments
1
0.2
ms/ms
2
0.4
ms/ms
3
0.6
ms/ms
4
0.8
ms/ms
5
1.0
ms/ms
C0365 DIS:CAN active
g
Input signal CAN active
0
CAN not active
1
CAN active
C0366 Sync response
1
System bus: Sync response
0
No response
1
Response to sync
No response
PLC responds to a sync telegram by sending the
CAN1_OUT object.
C0367 Sync Rx Id
128
System bus: Sync Rx identifier
Receive identifier of the sync telegram.
1
{1}
256
C0368 Sync Tx Id
128
System bus: Sync Tx identifier
Transmit identifier of the sync telegram.
1
{1}
256
C0369 Sync Tx Time
0
System bus: CAN sync send telegram cycle
·
A sync telegram with the identifier of C0368 is sent
with the set cycle time.
0
{1}
65000
0 = Off
C0370 Gateway addr.
0
System bus: Activate remote parameterisation
·
With a setting
¹ 0 all code write/read accesses are
redirected to the system bus node with the node
address set here.
·
The corresponding code is accessed via parameter
data channel SDO1 of the target device.
0
{1}
63
0 = Remote parameterisation deactivated