9300 servo plc, System blocks, 14 sd6 − motor temperature sensor monitoring – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 93: 15 sd7 − absolute value encoder monitoring

Advertising
background image

9300 Servo PLC

System blocks

2.12

MCTRL_MotorControl (node number 131)

2−79

L

9300 Servo PLC EN 5.0

2.12.17.14 Sd6 − motor temperature sensor monitoring

This monitoring function checks whether the motor temperature sensor supplies values within the
measuring range of −50 ... +250 °C.

If the values are out of this measuring range, monitoring is triggered.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x086 Sd6

Thermal sensor error

MCTRL_bSensorFault

·

ь

ь

· Lenze setting

ü Setting possible

·

The response is set under C0586:

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0594 MONIT SD6

à

Monitoring configuration: Motor
temperature sensor error
(X7 or X8)

à

Dependent on C0086

0

TRIP

2

Warning

3

Off

2.12.17.15 Sd7 − absolute value encoder monitoring

This monitoring function repeatedly reads in the absolute value of the encoder when the PLC is
switched on to find out if the same value is transmitted to the drive.

If a deviation > 5 % is detected at the motor shaft, the monitoring (TRIP) is actuated.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x087 Sd7

Absolute value encoder error

MCTRL_bEncoderFault_b

·

· Lenze setting

ü Setting possible