Aif1_io_automationinterface (node number 41), Inputs_aif1, 9300 servo plc – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 16: System blocks, 1 inputs_aif1, 1 aif1_io_automationinterface (node number 41)

Advertising
background image

2.1

AIF1_IO_AutomationInterface (node number 41)

9300 Servo PLC

System blocks

2−2

L

9300 Servo PLC EN 5.0

2.1

AIF1_IO_AutomationInterface (node number 41)

2.1.1

Inputs_AIF1

This SB is used as an interface for input signals (e.g. setpoints/actual values) from attached fieldbus
modules (e.g. INTERBUS, PROFIBUS−DP).

·

The process image is

– created in the cyclic task in a fixed time interval of 10 ms.

– created in an interval task within the time set for this task.

– read at the beginning of the task and written at its end.

Tip!

Please observe the Operating Instructions for the attached fieldbus module.

Inputs_AIF1

AIF1_nInW1_a

C0856/1

16 Bit

C0855/2

16 binary

signals

C0857

16 Bit

LowWord

16 Bit

HighWord

AIF1_dnInD1_p

16 Bit

AIF1_wDctrlCtrl

AIF1_bCtrlB0_b

AIF1_bCtrlB1_b

AIF1_bCtrlB2_b

AIF1_bCtrlQuickstop_b

AIF1_bCtrlB4_b

AIF1_bCtrlB5_b

AIF1_bCtrlB6_b

AIF1_bCtrlB7_b

AIF1_bCtrlDisable_b

AIF1_bCtrlCInhibit_b

AIF1_bCtrlTripSet_b

AIF1_bCtrlTripReset_b

AIF1_bCtrlB12_b

AIF1_bCtrlB13_b

AIF1_bCtrlB14_b

AIF1_bCtrlB15_b

16 Bit

16 binary

signals

16 Bit

C0855/1

16 binary

signals

AIF1_nInW2_a

C0856/2

C0856/3

AIF1_bInB0_b

AIF1_bInB15_b

AIF1_nInW3_a

AIF1_bIn16_b

AIF1_bIn31_b

Automation

Interface

Byte

1

Byte

2

Byte

3

Byte

4

Byte

5

Byte

6

Byte

7

Byte

8

Controlword

Fig. 2−1

Inputs_AIF1

Advertising