DCTRL_DriveControl (node number 121)

This SB controls the transition of the 9300 Servo PLC to certain states (e.g. TRIP, TRIP−RESET, quick
stop (QSP) or controller inhibit (CINH)).

·

The process image is created in the course of a fixed system task (interval: 2 ms).

STAT

C0136/1

DCTRL_wCAN1Ctrl

QSP

DISABLE

CINH

TRIP-SET

TRIP-
RESET

1

DCTRL_bTrip_b

DCTRL_bWarn_b

DCTRL_bMess_b

DCTRL_bFail_b

DCTRL_bCwCCw_b

DCTRL_bExternalFault_b

DCTRL_bNActEq0_b

DCTRL_bStat1_b

DCTRL_bStat2_b

DCTRL_bStat4_b

DCTRL_bStat8_b

DCTRL_bInit_b

DCTRL_bImp_b

DCTRL_bCInh_b

DCTRL_bRdy_b

DCTRL_bQspIn_b

1

>

16 Bit

Bit3

Bit3

C135.B3

C0135

Bit8

Bit8

C135.B8

1

>

Bit9

Bit9

C135.B9

X5/28

1

>

Bit10

Bit10

C135.B10

Bit11

C135.B11

Bit11

16

C0878/1

C0878/2

DCTRL_wAIF1Ctrl

DCTRL_bCInh1_b

DCTRL_bCInh2_b

DCTRL_bTripSet_b

DCTRL_bTripReset_b

C0878/3

C0878/4

DCTRL_bImp_b

DCTRL_bNActEq0_b

DCTRL_bCInh_b

DCTRL_bStat1_b

DCTRL_bStat2_b

DCTRL_bStat4_b

DCTRL_bStat8_b

DCTRL_bWarn_b

DCTRL_bMess_b

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

DCTRL_bStateB0_b

DCTRL_bStateB2_b

DCTRL_b

_b

StateB3

DCTRL_b

_b

StateB4

DCTRL_bStateB5_b

DCTRL_bStateB14_b

DCTRL_bStateB15_b

DCTRL_DriveControl

1

>

1

>

>

DCTRL_wStat

C0150

16 Bit

DCTRL_wFaultNumber

Fig. 2−13

DCTRL_DriveControl

Tip!

The SB DCTRL_DriveControl only affects the motor control and drive control of the
9300 Servo PLC, i.e. motor control/drive control and application program of the PLC are completely
independent of each other as long as the signals are not queried in the application program.

·

If, for instance, the motor control initiates a TRIP, the application program will not be stopped!

·

If, however, a TRIP is caused by a task overflow, the application program of the PLC will be
stopped as well!