Outputs_analog1 (analog output), 9300 servo plc, System blocks – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 33: Stop, 2 outputs_analog1 (analog output)

Advertising
background image

9300 Servo PLC

System blocks

2.5

ANALOG1_IO (node number 11)

2−19

L

9300 Servo PLC EN 5.0

Terminal assignment

·

Set via C0034 whether the input is to be used for a master voltage or a master current.

·

Set jumper bar X3 according to setting in C0034:

Stop!

Do not plug the jumper on 3−4! The PLC cannot be initialised in this case.

Terminal

Use

Jumper X3

Measuring range

X6/1, 2

Differential input for
master voltage

6

4

2

5

3

1

C0034 = 0
Level:
Resolution:
Scaling:

−10 V ... +10 V
5 mV (11 bits + sign)
±10 V º ±16384 º ±100 %

Differential input for
master current

6

4

2

5

3

1

C0034 = 1
Level:
Resolution:
Scaling:

+4 mA ... +20 mA
20

mA (10 bits without sign)

+4 mA

º 0 º 0 %

+20 mA

º +16384 º +100 %

C0034 = 2
Level:
Resolution:
Scaling:

−20 mA ... +20 mA
20

mA (10 bits + sign)

±20 mA º ±16384 º ±100 %

2.5.2

Outputs_ANALOG1 (analog output)

The output can be used as a monitor output. Internal analog signals can be output as voltage signals
via terminal X6/62 and used, for instance, as display values or setpoints for slave drives.

Outputs_ANALOG1

AOUT1_nOut_a

C0434

X6

62

Fig. 2−10

Outputs_ANALOG1

System variables

Variable

Data type

Signal type

Address

Display

code

Display

format

Note

AOUT1_nOut_a

Integer

Analog

%QW11.0

C0434

dec [%]

Analog output 1

Terminal assignment

Terminal

Use

Measuring range

X6/62

Analog output 1 (monitor 1)

Level:
Resolution:
Scaling:

−10 V ... +10 V (max. 2 mA)
20 mV (9 bits + sign)
±10 V º ±16384 º ±100 %

X6/7

Internal ground, GND