9300 servo plc, Appendix, 6 code table – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 125

Advertising
background image

9300 Servo PLC

Appendix

3.6

Code table

3−23

L

9300 Servo PLC EN 5.0

Code

Info

Possible settings

LCD

Code

Info

Selection

Lenze

LCD

C0061 Heatsink temp

g

Heatsink temperature

0

{1 °C}

100

C0063 Mot temp

g

Motor temperature

0

{1 °C}

200

C0064 Utilization

g

Controller load I x t during the last 180 seconds

·

C0064 >100 % trips OC5.

·

TRIP−RESET is only possible if C0064 < 95 %.

0

{1 %}

150

C0066 Motor load

g

I

2

× t−utilisation of the motor

0

{1 %}

250

C0067 Act trip

g

Current TRIP
("0" is displayed for FAIL−QSP, warning and message.)

C0070 Vp speed CTRL

à

Proportional gain of speed controller (V

pn

)

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

0.0

{0.5}

255.0

C0071 Tn speed CTRL

à

Reset time of speed controller (T

nn

)

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

1.0

{0.5 ms}

600.0

>512 ms = switched off

C0072 Td speed CTRL

0.0

Derivative gain of speed controller (T

dn

)

0.0

{0.1 ms}

32.0

C0075 Vp curr CTRL

à

Proportional gain of current controller (V

pi

)

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

0.00

{0.01}

15.99

C0076 Tn curr CTRL

à

Reset time of current controller (T

ni

)

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

0.5

{0.1 ms}

2000.0

2000 ms = switched off

C0077 Vp field CTRL

0.25

Proportional gain of field controller (V

pF

)

0.00

{0.01}

15.99

C0078 Tn field CTRL

15.0

Reset time of field controller (T

nF

)

1.0

{0.5 ms}

8000.0

8000 ms = switched off

[C0081] Mot power

à

Rated motor power according to nameplate

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

·

Change sets C0086 = 0

0.01

{0.01 kW}

500.00

[C0084] Mot Rs

à

Stator resistance of the motor

à

Dependent on C0086

·

If C0086 is changed, the value is reset to the assigned
Lenze setting.

·

Change sets C0086 = 0.

0.00

{0.01

W}

100.00