9300 servo plc, System blocks, 1 oc1 − short−circuit monitoring – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 80: 2 oc2 − earth−fault monitoring

Advertising
background image

2.12

MCTRL_MotorControl (node number 131)

9300 Servo PLC

System blocks

2−66

L

9300 Servo PLC EN 5.0

2.12.17.1

OC1 − short−circuit monitoring

This monitoring function protects the drive controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x011 OC1

Short circuit

MCTRL_bShortCircuit_b

·

· Lenze setting

ü Setting possible

Monitoring is actuated in the event of a short circuit in the motor phases. This can also be caused
by an interturn fault in the machine.

·

Monitoring can also respond during power−up if an earth fault occurs.

·

If monitoring responds, the drive controller has to be disconnected from the mains and the
short circuit has to be eliminated.

2.12.17.2

OC2 − earth−fault monitoring

This monitoring function protects the drive controller.

Error

Monitoring function

System variable

Possible responses

No.

Display

TRIP

Message

Warning

FAIL−QSP

Off

x012 OC2

Earth fault

MCTRL_bEarthFault_b

·

· Lenze setting

ü Setting possible

The 9300 Servo PLC is equipped with earth−fault detection as standard.

·

If monitoring is actuated, the drive controller has to be disconnected from the mains and the
earth fault has to be eliminated.

Possible causes of an earth fault:

·

Short circuit to frame of the machine

·

Short circuit of a phase to the shield

·

Short circuit of a phase to PE