2.9

DFOUT_IO_DigitalFrequency (node number 22)

9300 Servo PLC

System blocks

2−36

L

9300 Servo PLC EN 5.0

Configuration of the digital frequency output signal

·

The type of the digital frequency output signal is configured under C0540:

Code

LCD

Possible settings

Info

Lenze

Selection

C0540 Function

2

Digital frequency output: Function

·

X9 is inhibited if 0, 1, or 2 have
been selected.

·

DFOUT_nIn_v = 0 if 4 or 5 have
been selected.

·

The input signals are buffered
electrically.

0

DFOUT_nOut_v as %

1

DFOUT_nOut_v as rpm

2

Incremental encoder simulation + zero pulse

4

X9 is output on X10

5

X8 is output on X10

C0540 = 0

Output of an analog signal

Function

The input signal DFOUT_nOut_v is interpreted as an analog signal [%] and is output as a frequency signal on the
digital frequency output X10.

Scaling

100 %

º (INT)16384 º C0011 (n

max)

Transmission function

f [Hz]

+ DFOUT_nOut_v [%] @ Strichzahl aus C0030

100

@

C0011 (n

max

)

60

DFOUT_nIn_v

+ f [Hz] @

60

Strichzahl aus C0030

@ 2

14

15000

Example

·

DFOUT_nOut_v

= 50 %

·

C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution

·

C0011 = 3000 rpm

f [Hz]

+ 50 % @ 2048

100

@ 3000

60

+ 51200 Hz

C0540 = 1

Output of a speed signal

Function

The input signal DFOUT_nOut_v is interpreted as a speed signal [rpm] and is output as a frequency signal on the
digital frequency output X10.

Scaling

15000 rpm

º (INT)16384

Transmission function

f [Hz]

+ DFOUT_nOut_v [rpm] @

Strichzahl aus C0030

60

Example

·

DFOUT_nOut_v

= 3000 rpm

·

C0030 = 3, this corresponds to a number of increments of 2048 increments/revolution

f [Hz]

+ 3000 rpm @ 2048

60

+ 102400 Hz

C0540 = 2

Encoder simulation of the resolver with zero track in resolver position

Function

·

The function is used if a resolver is connected to X7.

·

The encoder constant for the output X10 is set under C0030.

·

The output of the zero pulse referring to the rotor depends on how the resolver is attached to the motor.

·

The zero pulse can be shifted by +360 ° under C0545 (65536 inc = 360 °).

C0540 = 4

Direct output of X9

Function

Use of X9 as a digital frequency input.

·

The input signal at X9 is electrically amplified and is directly output to X10.

·

The signals depend on the assignment of input X9.

·

C0030 and C0545 have no function.

·

The zero track is only output if it is also connected to X9.

C0540 = 5

Direct output of X8

Function

Use of X8 as an input for incremental encoders or sin/cos encoders.

·

The input signal at X8 is electrically amplified and is directly output to X10.

·

The signals depend on the assignment of input X8.

·

C0030 and C0545 have no function.

·

The zero track is only output if it is also connected to X8.