ANALOG1_IO (node number 11)

9300 Servo PLC

System blocks

2−18

L

9300 Servo PLC EN 5.0

2.5

ANALOG1_IO (node number 11)

2.5.1

Inputs_ANALOG1 (analog input)

The input is the interface for differential analog signals between terminals X6/1, 2. It can be used as
a setpoint input or as an actual value input.

Inputs_ANALOG1

AIN1_nIn_a

C0400

AIN1_bError_b

1

2

C0034

X6

Fig. 2−9

Inputs_ANALOG1

System variables

Variable

Data type

Signal type

Address

Display

code

Display

format

Note

AIN1_nIn_a

Integer

Analog

%IW11.0

C0400

dec [%]

Analog input 1

AIN1_bError_b

Bool

Binary

%IX11.1.0

Only when C0034 = 1:
TRUE if

½I½ < 2 mA

Selection of master voltage/master current

·

C0034 can be used to set whether the input is to be used for a master voltage or a master
current:

Code

LCD

Possible settings

Info

Lenze

Selection

C0034 Mst current

0

Selection: Master voltage/master
current

0

−10 V ... + 10 V (master voltage)

1

+4 mA ... +20 mA

(master current)

2

−20 mA ... +20 mA

·

Please also observe the jumper position X3 at the front of the 9300 Servo PLC in this
connection (see terminal assignment).

Use as a 4 ... 20 mA master current input

·

If the input is used as a master current input (C0034 =1), then AIN1_bError_b = TRUE as long
as the absolute value of the master current is < 2 mA, otherwise it is FALSE.

·

C0598 can be used to set the response for the case that the absolute value of the master
current is < 2 mA:

Code

LCD

Possible settings

Info

Lenze

Selection

C0598 MONIT SD5

3

Monitoring configuration:
Absolute master current value across
X6/1, 2 < 2 mA

0

TRIP

2

Warning

3

Off