Signal types and scalings, 9300 servo plc, Preface and general information – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual

Page 14: 7 signal types and scalings

Advertising
background image

9300 Servo PLC

Preface and general information

1−8

l

9300 Servo PLC EN 5.0

1.2.7

Signal types and scalings

Most inputs and outputs of Lenze function blocks/system blocks can be assigned to a certain signal
type. We distinguish between digital, analog, position and speed signals.

The identifier of the corresponding input/output variable has an ending (starting with an underscore).
It indicates the signal type.

Signal type

Ending

Memory
space

Scaling
(external value

º internal value)

Previous
identification

Analog

_a

(analog)

16 bits

100 %

º 16384

H

Digital

_b

(binary)

8 bits

0

º FALSE; 1 º TRUE

G

Phase difference or speed

_v

(velocity)

16 bits

15000 rpm

º 16384

F

·

Phase difference/speed ref. to 1 ms

·

Scaling example:

1 motor revolution + 65536 [inc]

Variable value (..._v) + 15000

60 [s]

@ 65536 [inc] + 15000

60000 [ms]

@ 65536 [inc] + 16384

ƪ

inc

ms

ƫ

Speed (on motor side) + 15000 [rpm] + 15000

60 [s]

Phase−angle or position

_p

(position)

32 bits

1 motor revolution

º 65536

E

ƒ

High Word

Low Word

0

31



‚

 Direction (0 º clockwise rotation; 1 º counter−clockwise rotation)

‚No. of motor revolutions (0 ... 32767)

ƒ Phase angle or position (0 ... 65535)

Note!

Due to their scaling, analog signals have an asymmetrical resolution range (−200 % ... +199.99 %):

External value:

−200 %

−100 %

0

+100 %

+199.99 %

Internal value:

−32768

−16384

0

+16384

+32767