DFOUT_IO_DigitalFrequency (node number 22)

2−37

L

9300 Servo PLC EN 5.0

Configuration of the encoder constant

·

The encoder constant of the encoder simulation can be set under C0030:

Code

LCD

Possible settings

Info

Lenze

Selection

C0030 DFOUT const

3

Encoder constant

0

256 increments per revolution

1

512 increments per revolution

2

1024 increments per revolution

3

2048 increments per revolution

4

4096 increments per revolution

5

8192 increments per revolution

6

16384 increments per revolution

C1799 DFOUT fmax

1250

DF_OUT_DigitalFrequency:
Maximum output frequency at X10
Note: The limitation of the maximum
output frequency at DFOUT is highly
non−linear. Hence:
C0540

£1: Upstream limitation of the

value "DFOUT_nOut_v"
C0540 >1: Limitation on the motor
side via C0011.
(The non−linear resolution of the
limitation has no effect on the transfer
function of the DfOut)

2.9.1.1

Technical data for the connection of X10

1

2
3
4
5
6
7
8
9

l = max. 50 m

0.14

0.14

0.5

26

26

20

mm

2

AWG

B

B

A

A

GND

Lamp control

Z

Z

X9



‚

1

2
3
4
5
6
7
8
9

1

2
3
4
5
6
7
8
9

1

2
3
4
5
6
7
8
9

X10

enable

B

B

A

A

GND

Z

Z

0.5

20

0.14

26

ƒ

The connection is to be carried out as
shown in the wiring diagram:

·

Use cables which are twisted and
shielded in pairs.

·

Connect the shield at both ends.

·

Observe specified cable cross−sections.

Fig. 2−20

Connection of digital frequency output X10 with digital frequency input X9

 Master drive
‚ Slave drive
ƒ Cable cross−sections to be used

Note!

Digital frequency input (X8/X9) and digital frequency output (X10) cannot be used independently of
each other, i.e. either X8 or X9 is output to X10 (C0540 = 4, 5).

·

If the configuration under C0540 selects another output for X10 (C0540 = 0, 1, 2), the digital
frequency inputs X8/X9 are deactivated.