2.7

DCTRL_DriveControl (node number 121)

9300 Servo PLC

System blocks

2−24

L

9300 Servo PLC EN 5.0

2.7.5

Controller inhibit (CINH)

This function sets "Controller inhibit (CINH)" in the drive, i.e. the power output stages are inhibited
and all speed/current/position controllers are reset.

·

The function can be controlled via the following 6 inputs (OR−linked):
– Terminal X5/28 (FALSE = controller inhibit active)
– Control word CAN1_wDctrlCtr of SB CAN1_IN
– Control word AIF_wDctrlCtrl of SB AIF1_IN
– Control word C0135, bit 9
– System variable DCTRL_bCInh1_b (TRUE = set controller inhibit)
– System variable DCTRL_bCInh2_b (TRUE = set controller inhibit)

·

C0136/1 indicates the control word C0135.

(

^ 2−23)

2.7.6

Setting TRIP (TRIP−SET)

This function sets "TRIP" in the drive and signals an "external error" (error message "EEr").

·

The function can be controlled via the following 4 inputs (OR−linked):
– Control word CAN1_wDctrlCtr of SB CAN1_IN
– Control word AIF_wDctrlCtrl of SB AIF1_IN
– Control word C0135, bit 10
– System variable DCTRL_bTripSet_b (TRUE = set TRIP)

·

C0136/1 indicates the control word C0135.

(

^ 2−23)

·

The response to TRIP can be set under C0581:

Code

LCD

Possible settings

Info

Lenze

Selection

C0581 MONIT Eer

0

Monitoring configuration:
External error

0

TRIP

1

Message

2

Warning

3

Off