9300 servo plc, Appendix – Lenze Drive PLC Developer Studio 9300 Servo PLC (V8.x) User Manual
Page 120

9300 Servo PLC
Appendix
3−18
L
9300 Servo PLC EN 5.0
Fault reset
The current fault can be reset by a TRIP−RESET e.g. via C0043:
Code
LCD
Possible settings
Info
Lenze
Selection
C0043 Trip reset
0
TRIP reset
0
TRIP−RESET (current TRIP reset)
1
Error occurred (TRIP is active)
Deleting entries in the fault memory
The entries in the fault memory can be deleted via C0167.
·
This function can only be used if there is no active fault.
Code
LCD
Possible settings
Info
Lenze
Selection
C0167 Reset failmem
0
Reset fault memory
0
No function
1
Delete all entries in history buffer
Access to fault memory via Global Drive Control (GDC)
The fault memory of the PLC can also be displayed in the GDC.
·
Double−click on "Dialog diagnostics" in the GDC parameter menu to open the 9300
diagnostics dialog box:
History buffer
No. of system error message and response (C0168/x)
Time of occurrence (C0169/x)
Frequency of successive occurrence (C0170/x)
Reset of the fault (TRIP−RESET); only possible if there is no active fault.