J29 emergency stop connections, J29 emergency stop connections 232, Cable specification – MTS Model FlexTest SE User Manual

Page 232

Advertising
background image

Models FlexTest® IIm/GT/SE Controller Hardware

J29 Emergency Stop Connections

FlexTest SE Controller Connections

232

J29 Emergency Stop Connections

Connector J29 E-STOP provides an output to external devices when an
emergency stop signal is generated. This connector may also be used with an
external E-stop.

Cable specification

15 contact type D male EMI connector.

Backshell–EMI metallized plastic.

Cable–24 AWG 4 connector with braided shield, with the braid connected to
a metallized plastic backshell at the chassis and to ground at the emergency
stop station.

J29 Connector Pin Assignments

P

IN

N

AME

F

UNCTION

1

xhead 24V

Fused +24V

2

xhead intlk com

24V common

3

Program interlock low
(xhead interlock low)

Low side of opto-isolator, jumpered to common

4

Program interlock high
(xhead interlock high)

High side of opto-coupler, pulled up to 24V (opto on = intlk)

5

Local E stop

Local E stop loop (connected to pin 7)

6

N/C

No connection

7

Local E stop

Local E stop loop (connected to pin 5)

8

HPU E stop

E stop loop from HPU (connect to pin 13)

9

N/C

No connection

10

N/C

No connection

11

N/C

No connection

12

xhead power

+24 V crosshead unlock power output (from HSM high relay
contact)

13

HPU E stop

E stop loop from HPU (connect to pin 8)

14

xhead power return

24 V common for crosshead unlock power output

15

N/C

Advertising