background image

Digital I/O Connections

Models FlexTest® IIm/GT/SE Controller Hardware

FlexTest IIm Controller Connections

197

Digital inputs

•

Digital inputs can be wired to allow the input from a switch contact, a relay

contact, or a logic signal.

•

All digital inputs are optically isolated at the Series 498 Digital I/O

transition module.

•

For example, an action defined in the can be selected, in the Station Setup
window’s Digital Input panel, as an Action.

•

The digital inputs are used by the Digital Input process in the MultiPurpose

TestWare application. They can also be monitored from the Station Manager

application.

•

You can use the Event-Action Editor window to define an action that occurs
in response to a digital input event. The defined action can then be selected
in the Station Setup window’s Digital Input panel.

•

Sixteen jumpers located on the Series 498 Digital I/O transition module allow

each input to be configured for a relay contact or logic signal.

•

Each digital input connector on the built-in Digital I/O Access panel (FlexTest

IIm) supports two channels.

•

Each digital input supports a differential TTL to +30 V DC signal or a

switch or relay contact switching the on-board 12 V supply.